Go to the content
PROFECTRONICS
Software

Test software and user interface

The software of a test bench includes the operator screen, sequence, control, limit values, calibration and test record. Profectronics programs in LabVIEW, Beckhoff, B&R and Siemens.

Example MK-12

P&ID of the conditioning unit MK-12

Conditioning unit in a container (40 ft) with 4 media circuits and 26 measurement points: water-glycol, thermal oil, chilled water, and nitrogen and compressed air.

MK-12 media conditioning · 4 circuits · 26 measurement points 01 · WATER / GLYCOL 30 % B-01 · TANK 400 l LI 01 — PU-01 · VFD PI 01 — F-01 PDI — WT-01 · PLATE CHW TI 03 — E-01 · 18 kW V-01 · 3-WAY FI 01 — TI 01 — QI 01 — TI 02 — PI 02 — 02 · THERMAL OIL B-02 · OIL 250 l PU-02 · GEAR PI 11 — E-02 · 24 kW WT-02 · OIL COOLER CHW TI 13 — V-02 FI 11 — TI 11 — TI 12 — PI 12 — 03 · CHILLED WATER KM-01 · 45 kW PS-01 · BUFFER 300 l PU-03 · VFD FI 21 — TI 21 — PI 21 — TO WT-01 · WT-02 FROM WT-01 · WT-02 TI 22 — 04 · N₂ AND COMPRESSED AIR N2 · 300 bar DR-01 PI 31 — MFC-01 FI 31 — SV-01 CA 8 bar DR-02 PI 32 — MFC-02 FI 32 — P-01 · TEST SPECIMEN · CUSTOMER SIDE TI 41 — TI 42 — MI 41 —
Fig. 1 · P&ID MK-12 with 4 media circuits and 26 measurement points, symbols to ISO 10628 and IEC 60617

The P&ID is an example. It does not show the measured values. The user interface shows the measured value at each measurement point.

User interface

6 views of the user interface

Each view shows the information for the next decision of the operator.

ViewContent
OverviewP&ID with the measured value next to each measurement point. A click on the measurement point shows the trend of the last 45 s. A line with flow changes its colour.
MeasurementPointer instruments with fine scale, warning mark and shutdown mark. A trend chart shows 4 channels over time with limit band and event marks. Update rate 2 Hz.
SequenceTest sequence in steps. Each step has a release chain and its own setpoints. A message list with time, class, source and acknowledgement goes with the sequence.
ControlControl loops with the parameters Kp, Ti and Td. Profectronics designs each loop on a process with first-order lag and dead time. The step response is shown against a tolerance band.
Limit valuesEach measurement point has its own limit with type, hysteresis, response delay and reaction. The hysteresis prevents a message that toggles at the limit.
CalibrationThe software converts the raw signal of the transducer into a measured value. Test points compare the characteristic curve with the tolerance.
Functions

Control, limit values and calibration in detail

The values below are examples from an acceptance specification. The functional specification sets the values of a unit.

Acceptance of a control loop (example)

  • Settling timemaximum 120 s to ± 0.5 K
  • Overshootmaximum 8 % of the step height
  • Control deviationsteady-state, less than 0.2 K
  • Reserve of the manipulated variableminimum 15 % in steady state

Settings for each limit value

  • Typeupper limit, lower limit or band
  • Operating statehome position, start-up, test run, shutdown
  • Reactionreport, warn, hold sequence, shut down
  • Acknowledgementthe message stays until confirmation

Effect of a limit value

  • The limit value applies only in the selected operating states. During start-up, a wider band applies than during the test run.
  • The reaction “shut down” stops the sequence in a controlled order. It is not an emergency stop. The emergency stop is hard-wired.
  • The change log of the unit saves each change with user, time stamp and old value.

Calibration methods

  • Two-point lineSlope and zero point from 2 test points, for transducers with a linear characteristic curve in the measurement range.
  • Characteristic tableSupport points with linear interpolation
  • Third-degree polynomialfor curved characteristic curves of transducers
  • Fixed valuefixed value for substitute operation

Example Pt100: tolerance to IEC 60751 class A: ± (0.15 + 0.002 · |t|) °C. If a test point is outside the tolerance, the software blocks the acceptance of the characteristic curve. The block stays until a new measurement of the point is available.

Design

Rules for the user interface

The screen shows the information for the next decision and no other information.

Platforms

Control platforms

Profectronics programs on the platform that the operator already uses in the plant. After the acceptance, the maintenance personnel of the operator can open the unit themselves.

PlatformLevelTools and use
LabVIEWMeasurement technology and test sequenceProfectronics used LabVIEW from its foundation and continues to use it: user interface, data acquisition, test sequence and record. TestStand for sequence control in series production, PXI and C Series for data acquisition, TDMS as the format for measured data.
BeckhoffPLCTwinCAT 3 with structured text to IEC 61131-3, TwinCAT HMI for the operator screen, EtherCAT as fieldbus, TwinSAFE for the safety level. Standard at Profectronics if measurement technology and control have a close connection.
B&RPLCAutomation Studio with mapp components, POWERLINK and openSAFETY. In plants with B&R as the standard, Profectronics makes all of the unit in this environment.
SiemensPLCTIA Portal with SIMATIC S7-1200 and S7-1500, SCL and ladder diagram, WinCC for visualisation, PROFINET and PROFIsafe. For plants with Siemens as the standard of the maintenance department.

Programming languages

Profectronics programs in the languages of IEC 61131-3. The task sets the language: control algorithms and calculation blocks in structured text, interlocks in ladder diagram, sequences in sequential function chart.

Handover

The handover includes the source code with comments, change log and library version. We do not lock a block. The maintenance personnel of the operator can open each block.

  • STStructured text
  • FBDFunction block diagram
  • LDLadder diagram
  • SFCSequential function chart
  • GLabVIEW
  • C#Evaluation and interfaces
  • PythonRecalculation and management of test equipment
Structure

Layers of the test software

The user interface is the top layer. Below it are the sequence, the control and the preparation of measured values. The safety is hard-wired and is outside the software.

Concept Suite

Concept Suite: concept from one source

The Concept Suite is a tool that Profectronics developed for its own use. From one source, it makes the P&ID, 3D model, signal list, circuit diagram and parts list.

P&ID with rule check

The Concept Suite checks the P&ID against rules. A proposal shows the deviations.

Screen · Concept Suite, P&ID with rule check

3D model from the P&ID

A change in the P&ID goes through to the 3D model. Output as STEP.

Screen · Concept Suite, 3D model from the P&ID

Simulation

Heat-up, hold and cool-down of an autoclave. 3D flow and heat transfer come from the same concept model. Hold at 200 °C with a heater jacket, cool-down with a blower at 2 m³/min.

Screen · Concept Suite, simulation of the hold phase at 200 °C

Outputs from one source

  • P&IDwith rule check
  • Proposalwith the deviations shown
  • 3D modelSTEP
  • Cause and effectSafety functions
  • DrawingsPDF, DXF
  • I/O list and signal listOPC UA
  • Circuit diagramIEC or NFPA 79
  • Parts listCSV

Same identifiers in all documents

P&ID, PLC and user interface use the same identifiers.

Sequence from the concept to the commissioning

Enquiry

Enquiry about software and user interface

For a first discussion, give the measurement points, sequences, records and the control platform in your plant. Tell us if you want to retrofit a unit that you already have or plan a new unit.

Send an enquiry Focus areas in test bench construction